Two grid power

Power Equipment Of Two Grids

DFW-12 outdoor ring main unit

Product overview:

● Prefabricated charged touchable silicone rubber cable head is adopted, which is fully sealed, fully insulated, maintenance free, and can reliably ensure personal safety; ● Compact structure, compact and beautiful appearance, stainless steel double-layer box body, with a service life of more than 20 years; ● On the premise of not affecting the operation of the main network, it realizes regional power outage maintenance and reduces the scope of power outage; ● One or more SF6 load switches can be equipped with flexible and diverse wiring modes, and the branch outgoing line can reach 8 circuits at most; ● Lightning arrester, short circuit fault indicator, current limiting fuse, etc. can be selected to meet various user requirements.

Product model description​

①

Outdoor ring main unit​

②

Number of incoming circuits

③

Number of outgoing circuits

④

Number of branch circuits​

⑤

Branch circuit with switch​

⑥

Number of branch circuit switches: one switch can be omitted without writing​


Technical parameter

No. Name Parameter
1 Rated Voltage 12kV
2 Rated Current 630A
3 Power frequency withstand voltage (phase to ground) 42kV/min
4 Lightning impulse Voltage 75kV
5 Rated breaking current 630A
6

Rated short-circuit switching current (peak value)​

50kA
7 Rated short-time withstand current 25kA/4S
8

Rated peak withstand current​

50kA
9

Rated breaking capacitive current​

45A
10

Rated breaking inductive current​

16A
11

Full load breaking times​

100
12

Mechanical operation times of opening and closing​

2000


Typical wiring scheme​

Model​

Wire number description​

Primary wiring diagram​

Outline dimension (L x W x H)​

DFW-102K

One in two branches with one switch​

  1180×1150×2300
DFW-103K

One in three branches with one switch​

1250×1150×2300
DFW-104K

One in four branches with one switch​

  1250×1150×2300
DFW-112K

One in one out two branches with one switch​

  1350×1150×2300
DFW-113K

One in one out three branches with one switch​

  1420×1150×2300
DFW-114K

One in one out four branches with one switch​

  1420×1150×2300
DFW-102K 2

One in two branches with two switches​

  1350×1150×2300
DFW-112K2

One in one out two branches with two switches​

  1500×1150×2300
DFW-103K3

One in three branches with three switches​

  1850×1150×2300
DFW-113K3

One in one out three branches with three switches​

​  2000×1150×2300


Outline Diagram​


​

Infrastructure Diagram​



Technical requirement​
● The inner side of the brick wall shall be plastered with 1:3 cement mortar and treated with waterproof treatment;
● The through beam adopts Φ6 concrete operation;
● Foundation channel steel shall be subject to anti-corrosion treatment after fabrication;
● After the installation of the branch box, the surrounding of the base shall be sealed with cement;     
● Waterproof measures shall be taken at the entrance of the hole
● The grounding electrode shall be embedded in the foundation, and the grounding resistance shall meet the requirements of the power department

Ordering Instructions
● Product model and primary drawing can be provided if users have special requirements;
● Standard section of incoming and outgoing lines and branch cables;
● Number of lightning arresters and short circuit fault indicators selected;
● Material and color of shell.