Product overview:
XGN□-12 fully insulated fully enclosed gas ring main unit products are widely used in 10kV/6kV power distribution systems and are the selected switch products for various urban and rural user power transformation and distribution systems. The switch cabinet is a modular unit mode, which can be combined according to different purposes; It consists of fixed unit combination and expandable unit to meet the flexible use needs of compact switchgear in various substations. XGN□-12 fully insulated fully enclosed gas ring main unit is a completely sealed system, and its live parts and switches are enclosed in the stainless steel body. The whole switch device is not affected by external environmental conditions, thus ensuring operation reliability and personal safety. And it is maintenance free. By selecting the extensible bus, any combination can be realized to achieve full modularization. The safety insulation and shielding of the extended bus ensure the reliability and safety. XGN□-12 fully insulated fully enclosed gas ring main unit can also provide TV based automation solutions, forming the concept of intelligent switch, and greatly reducing the on-site installation and commissioning workload. XGN□-12 fully insulated fully enclosed gas ring main unit is classified into non- expanded standard configuration and expandable standard configuration. Due to the combination of full module and half module and self expandability, it has very special flexibility. XGN□-12 fully insulated fully enclosed gas ring main unit shall comply with GB standard. The design life of operation under indoor conditions (20℃) exceeds 30 years.
Product model description
① | Fully insulated fully enclosed gas ring main unit |
② | Rated Voltage:12 Rated Voltage 12kV;24 Rated Voltage 24kV |
③ | Cabinet type name: C: load switch cabinet; F: Fuse combination cabinet; V: Vacuum circuit breaker cabinet;SV, SL, bus section cabinet; M: Metering cabinet; PT: PT cabinet (A total cabinet is composed of any combination of C,F, V, SV and SL) |
④ | Rated Current:630 Rated Current 630A;1250 Rated Current 1250A |
⑤ | Extension type: 1: Left extension; D: Right extension; ID: both sides extension; Blank: Not extensible |
⑥ | Cable inlet and outlet mode: L: left cable inlet and outlet; R: Right cable inlet and outlet; LR: cable inlet and outlet on both sides Blank: front inlet and outlet |
Example:
1.XGN□-12-C/630DL refers to load switch cabinet, with rated voltage of 12kV, rated current of 630A, right extension and left cable incoming and outgoing mode.Main features of the product
● Technical description
XGN□-12 fully insulated fully enclosed gas ring main unit is installed on a galvanized sheet frame, the switch unit is in the SF6 gas box, and the gas box is made of anti-corrosion and non-magnetic 3mm thick stainless steel plate. SF6 gas box is a "seal pressure system" which can operate for 30 years under normal working conditions. The pressure of SF6 gas under normal operation is 0.15~0.4 bar. The gas box is equipped with a pressure relief device to ensure that the gas can be released from the bottom or rear when the pressure is too high.
● Switch unit
The load switch adopts the coaxial rotary double breakpoint mode, and carries out kinetic energy operation through the same operation hole in coordination with the sliding plate. Therefore, the switch can only be in one of the three states of "closing, opening, and grounding" at any time to completely avoid misoperation.
● Operating mechanism
The operating mechanism of the switch is installed at the front outside the air box, which has been treated with special technology to prevent corrosion, facilitate manual operation and maintenance, and easily realize electric operation.
Unit code |
Significance |
Unit code |
Significance |
C | Standard single bushing load switch unit |
- | Busbar top bushing |
F | Switch-fuse combination unit |
SL | Buscouple unit |
V | Circuit breaker unit |
M | Metering unit |
D | Cable incoming unit (without switch) |
PT | PT unit |
+ | Busbar side bushing |
1K2(4) | Load switch unit with double bushing |
Performance indicators
SF6 gas pressure: absolute pressure 1.4BAR at 20℃
Annual gas leakage rate: ≤0.2% per year
Protection grade: IP67
Stainless steel thickness of air chamber: 3.0mm
Normal operating environmental conditions
Maximum temperature: 40℃
Minimum temperature: - 40℃
Maximum average relative humidity: ≤95%
Altitude: ≤2000m
Busbar
Busbar in switch cabinet: 400mm2 Cu
Grounding busbar of switch cabinet: 150mm 2Cu
Colour
Front panel of switch cabinet: RAL7012
Side plate and front cover plate of cable room: RAL7035
Technical parameter
Model |
C module | F module | V module | CB module | |||
Composite switch |
Combined electrical apparatus |
Vacuum switch |
Isolating/grounding switch |
Vacuum circuit breaker |
Isolating/grounding switch |
||
Rated Voltage | kV | 12 | 12 | 12 | 12 | 12 | 12 |
Rated frequency |
Hz | 50 | 50 | 50 | 50 | 50 | 50 |
Power frequency withstand voltage (phase-to-phase/isolating distance) |
kV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
Lightning impulse withstand voltage |
kV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
Rated Current | A | 630 | Note 1) |
630 | 1250/630 | ||
Rated closed-loop breaking current |
A | 630 | |||||
Rated cable charging breaking current |
A | 135/135 | |||||
Rated short-circuit making current (peak value) |
A | 50 | 80 | ||||
Rated peak withstand current |
kA | 50 | |||||
Rated short-time withstand current | kA/3s | 20 | |||||
Rated short-circuit breaking current |
kA | 31.5 | 20 | 25 | |||
Rated transfer current |
A | 1750 | |||||
Maximum current of matched fuse |
A | - | 125 | ||||
Circuit resistance |
-n | ≤300 | ≤600 | ||||
Mechanical life | times | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 |
Note: 1) It depends on the current rating of the fuse
Structure and installation dimension drawing