Product overview:
This product fully complies with GB17467 High-voltage/Low-voltage prefabricated substation. It is applicable to urban public power distribution, street lamp power distribution, industrial and mining enterprises, urban buildings, residential quarters, oil field terminals, hotels, parks and construction sites, etc., and can realize looped network or terminal power supply.Product model description
① | Prefabricated substation |
② | Structural features: P-品 shaped; M-目shaped |
③ | Design No. |
④ | Rated voltage at high voltage side (kV) |
⑤ | Rated voltage at low voltage side (kV) |
⑥ | Rated capacity of transformer (kVA) |
Conditions of use
● Altitude: ≤1000m;
Technical parameter
No. | Name | Unit |
High voltage apparatus |
Transformer |
Low voltage apparatus |
1 | Rated Voltage | kV | 6/10 | 60/0.4 10/0.4 | 0.4 |
2 | Rated capacity |
kVA | 50~1600 | ||
3 | Rated Current | A | 200、400、630 | 100~3200 | |
4 | Rated short-circuit breaking current |
A | Load switch 400-600 |
15~63kA | |
kA | Combination switch depends on fuse |
||||
5 | Rated short-time withstand current | kA | 16,20(4s) | 15(1s) | |
30(1s) | |||||
6 | Rated peak withstand current |
kA | 31.5,50 | 30 | |
63 | |||||
7 | Power frequency withstand voltage (1min) | kV | Phase to ground and interphase 32/42 |
25/35( oil immersed ) | ≤0.3,2 |
Isolating distance36/48 |
20/28( dry type ) | ● 0.3,2.5 | |||
8 | Lightning impulse withstand voltage (peak value) |
kV | Phase to ground and interphase 60/75 |
60/75 | |
Isolation distance 70/85 |
|||||
9 | Cabinet protection grade |
||||
10 | Noise level |
ab | IP23 | ||
11 | Executive standards |
GT/T 17467 High-voltage/Low-voltage prefabricated substation |
55 | ||
DL/T537 Technical Conditions for Ordering 6-35kV Box type Substation |
Note: Items 5 and 6 are not required when the transformer capacity is less than 200kVA.
Installation dimension drawing
Example of some product outline drawings